PMU Connection Tester "Connection closed by remote device"

$
0
0

Anytime i try to use the Connection Tester to connect to a PDC, after a couple of seconds I get the error “Connection closed by remote device”


I didn´t have any issues before, so I don´t know what the problem is.

NOTE: In my configuration I have 2 PMUs connected to a PDC, problem only lies in connecting to said PDC, because if I connect the PMU directly to my machine, there is no issue.
NOTE2: I have ForceIPv4 to True

2 posts - 2 participants

Read full topic


Receiving C37-118 UDP data

$
0
0

Hi,

I am using a SEL-735 device. The device has a capability to send continuous waveform data using C37-118 protocol using UDP at 3ksps. I am trying to test it using PMU connection tester, but I am getting a error. Below is the error I am receiving.

“Attempting connection to “ID 1 using IEEE C37.118.2-2011 over Udp” at 02/05/2025 10:26:53 using IEEE C37.118.2-2011
Exception: Attempting to realign parsing to found protocol sync-byte after parsing exception: Bad data stream, expected sync byte 0xAA as first byte in IEEE C37.118 frame, got 0x00
Exception: Probable frame misalignment detected, forcing scan ahead to next sync byte
Exception: Attempting to realign parsing to found protocol sync-byte after parsing exception: Bad data stream, expected sync byte 0xAA as first byte in IEEE C37.118 frame, got 0x00
Exception: Probable frame misalignment detected, forcing scan ahead to next sync byte
Exception: Attempting to realign parsing to found protocol sync-byte after parsing exception: Bad data stream, expected sync byte 0xAA as first byte in IEEE C37.118 frame, got 0xDC”

Thanks,
Rabi Kar,

3 posts - 2 participants

Read full topic